This instruction show you guide on how to repair Perkins 1106D electric power generation (EPG) cranks but will not start with high press fuel system trouble.
Preparations:
Newest Perkins EST 2022A & 2019A Full Support Free Download
Perkins SPI2 2018A EPC+Service Manual Free Download
Procedures:
1.Use the Perkins electronic service tool to check the absolute fuel rail pressure while the engine is cranking at a minimum speed of 150 rpm.
2.If the absolute fuel rail pressure is less than 25 MPa (3625 psi), perform the following
procedure:
a.Check that the inlet pressure at the fuel rail pump is greater than 50 kPa (7.25 psi). If the inlet pressure is less than 50 kPa (7.25 psi),repeat the diagnostic process from